With the rapid development of China power industry, electrical preventive experiment is an important aspect of electrical power system safe operation and maintenance work. Insulation diagnosis is an important tool to detect the in sulation or fault of electrical equipment
Currently, electrical equipment (such as transformers, generators, etc.) toward the trend of large capacity, high voltage, structural diversification and sealing, this requires insulation resistance tester with advantages of large capacity, strong anti-interference ability, easy to carry and so on. So we designed and developed the series meter especially for strong interference field test for large high voltage transformers, electrical appliances, remote power cables or laying cables and other electrical insulation resistance properties for high-voltage substations, power plants and others.
The instrument system combines analog circuits, digital circuits, mechanically operated advantages, achieved a leading position at the output voltage, output current, measuring range, measurement accuracy, anti-interference ability.
Mode | Test voltage | Voltage accuracy | Short-circuit current |
GM-5kV | 0.25,0.5,1,2.5,5kV | ±(5%+10V) | 10mA |
GM-10kV | 0.5,1,2.5,5,10kV | ±(5%+10V) | 10mA |
GM-15kV | 1,2.5,5,10,15kV | ±(5%+10V) | 10mA |
GM-20kV | 0.5,1,2.5,5,10,20kV | ±(5%+10V) | 10mA |
Range | Resistance measurement range | Accuracy |
20MΩ/500V | 0.5~19.99 MΩ | ±(5%+5digital) |
200MΩ/1000V | 5.0~199.9 MΩ | ±(5%+5digital) |
2GΩ | 0.05~1.999 GΩ | ±(5%+5digital) |
20GΩ | 0.5~19.99 GΩ | ±(5%+5digital) |
200GΩ | 5.0~199.9 GΩ | ±(10%+10digital) |
2000GΩ | 50~1999 GΩ | Less than 1000GΩ ± (20% + 10 digital) (humidity ≤70%) |
Anti-electric field interference ability | 2mA(50Hz) | |
Timekeeping and alarm function | maximum value of stopwatch is 19 minutes and 59 seconds. 20 minutes for a cycle. The stopwatch will tell the time at these time points: 15 seconds, 60 seconds and every 60 seconds. When telling time, resistance readings hold for 5 seconds. If the measured resistance is below the lower limit of range, the reading is invalid and the instrument will continuously sound to give an alarm | |
Display | three and a half bits LCD digital meter (three), respectively show test voltage, test resistance, test time | |
Power supply |
10×1.2Vbattery(2000mAh Ni-MH rechargeable battery), total DC12V power supply
AC: 220V (50/60Hz) |
|
Operating Conditions | Temperature:0~40ºC | Relative humidity:20~90% |
Dimension | 315×240×155mm 3 | |
Weight | 5kg |