Commercial Hybrid Inverter
(Built-in Transformer)
LEI-30K / 50K / 60K / 100K / 125K / 150K-TT
Product Features
*Can be used in high-altitude, alpine areas
*Multi-channel PV MPPT access to improve power generation utilization
*Power frequency topology, industrial design
*Wide DC input voltage range
design, compatible with various batteries
*High-performance DSP, optimized control circuit design, better performance
*Intelligent management control strategy, multiple working modes, online or remote switching
*Cold start with load, three-phase 100% unbalanced load, strong load adaptability
*Support diesel generator access, seamless switching between on-grid and off-grid (optional)
*AC and DC dual power backup, ensure the power supply of the control system
| Model | LEI- 3 0K-TT | LEI-50K-TT | LEI-60K-TT | LEI-100K-TT | LEI-120K-TT | LEI-150K-TT |
| DC Input (PV) | ||||||
| Max. Input Voltage [V] | 850 | |||||
| MPPT Voltage Range [V] | 600 ~ 850 | |||||
| Number of MPPTs | 3 | |||||
| Max. Input Power Per MPPT [kW] | 10 | 20 | 30 | |||
| DC Input (Battery) | ||||||
| Battery Type | Lithium, Lead-Carbon, Lead Acid etc | |||||
| Operating Voltage Range [V] | 320 ~ 600 | 400 ~ 600 | ||||
| AC Output (Grid-side) | ||||||
| Rated Output Power [kW] | 30 | 50 | 60 | 100 | 125 | 150 |
| Max. Output Apparent [kVA] | 33 | 55 | 66 | 110 | 137 | 165 |
| Rated Grid Voltage [V] | 3/N/PE,230/400 | |||||
| Rated Grid Frequency [Hz] | 50/60 | |||||
| AC Output (Loads) | ||||||
| Rated Output Power [kW] | 30 | 50 | 60 | 100 | 125 | 150 |
| Max. Output Apparent [kVA] | 33 | 55 | 66 | 110 | 137 | 165 |
| Overload Capacity | 110% for Ten Minutes, 120% for One Minutes | |||||
| Rated Grid Voltage [V] | 3/N/PE,230/400 | |||||
| Rated Grid Frequency [Hz] | 50/60 | |||||
| THDi | <3%(Rated Output Power) | |||||
| Unbalanced Load Capacity | 100% | |||||
| Protection | ||||||
| AC Short Circuit Protection | Yes | |||||
| DC Reverse Polarity Protection | Yes | |||||
| Surge Protection | Yes(PV-side & Grid-side) | |||||
| Efficiency | ||||||
| Max. Efficiency | 92% | 93.0% | 94.0% | |||
| General Data | ||||||
| Dimensions (W*D*H)[mm] | 950*700*1953 | 1200*800*2050 | ||||
| Net Weight [kg] | 650 | 650 | 800 | 900 | 1050 | 1250 |
| Isolation Transformer | Yes | |||||
| Operating Temperature Range [ºC] | -30 ~ +55 | |||||
| Shutdown Self power Consumption [W] | <50 | |||||
| Cooling Mode | Forced air cooling | |||||
| Installation Style | Cabinet Installation | |||||
| Ingress Protection | IP20 | |||||
| Relative Humidity | 0 ~ 95%,non-condensing | |||||
| Max. Altitude [m] | 5000(>3000 Derating) | |||||
| Display Mode | Touch screen | |||||
| Dispatching Communication Mode | Ethernet,RS48 | |||||
| BMS Communication Mode | RS485,CAN | |||||
| Communication Protocol | Modbus-RTU/TCP | |||||