TECHNICAL DATA SHEET
FOR 15MVA, 33/11kV
DISTRIBUTION POWER TRANSFORMER
| ITEM | DESCRIPTION | UNIT | REQUIRED | GAURANTEED | 
| 1. | Manufacturer | HEMG | ||
| 2. | Country of manufacture | 
 | CHINA | |
| 3. | Type of transformer | 
 | Three Phase Step Down Power Transformer | Three Phase Step Down Power Transformer | 
| 4. | Standard and tolerances | 
 | IEC 60076 | IEC 60076 | 
| 5. | Installation | 
 | Outdoor | Outdoor | 
| 6. | Insulation fluid | 
 | Mineral oil (type NYNAS 10 GBX) | Mineral oil (type NYNAS 10 GBX) | 
| 7. | Type of preservation | 
 | Conservator with air breather | Conservator with air breather | 
| 8. | Type of cooling | 
 | ONAN | ONAN | 
| 9. | Type of core (shell type/core type) | 
 | Core Type | Core Type | 
| 10. | Rated power (ONAN/ONAF) | MVA | 15 | 15 | 
| 11. | Rated voltages at no-load - HV side - LV side | kV kV | 33 / 11 | 33 / 11 | 
| 12. | Rated frequency | Hz | 50 | 50 | 
| 13. | Type of tap changer on HV side | 
 | On-load (ABB type UZ) | On-load (ABB type UZ) | 
| 14. | Type of regulation | 
 | CFR | CFR | 
| 15. | Number of taps | 
 | 17 (+,-8 x 1.25%) | 17 (+,-8 x 1.25%) | 
| 16. | Vector group | 
 | YD1 | YD1 | 
| 17. | Temperature rise: - Top oil - Windings - Hot spot | K K K | 45 55 68 | 45 55 68 | 
| 18. | Impedance voltage | % | 10% at 15MVA, 33/11kV base | 10% at 15MVA, 33/11kV base | 
| 19. | No load loss at rated voltage | KW | 13 | 13 | 
| 20. | Load loss at nominal tap | KW | 76 | 76 | 
| 21. | Auxiliary loss | KW | N/A | N/A | 
| 22. | Flux density at nominal tap | T | <1.72 | <1.72 | 
| 23. | No load current at nominal tap | % | 0.22 | 0.22 | 
| 24. | Lightning Impulse test voltage - Full wave (peak) (Acc. To IEC 60076-3) - HV winding - HV Neutral - LV winding | kVp kVp kVp | 650 - 170 | 650 - 170 | 
| 25. | Short-duration induced AC withstand voltage - HV - LV | kV | 70, 22 | 70, 22 | 
| 26. | Separate source AC withstand voltage test, (Acc. to IEC 60076-3) - HV winding - LV winding | kV | 38 70 | 38 70 | 
| 27. | Sound Pressure level (ONAN/ONAF) | dB | 62 | 62 | 
| 28 | Overload/Fault current capability | kA | Accr. to IEC 354 | Accr. to IEC 354 | 
| 29. | Basic Insulation level | M | LI 650 AC 170 / 75 (Phase) | LI 650 AC 170 / 75 (Phase) | 
| 30. | Short Circuit Impedances: Lowest tap Highest tap | /phase /phase | After Placement of Order | After Placement of Order | 
| 31. | Physical Dimensions | W x L x H | 4650*3700*4000MM | |
| 32. | Total Quantity of Oil required | kg | 8650KG | |
| 33. | Filling Medium of Tank for shipment If oil, state the quantity required | Ltrs | Transformer will be shipped with oil | |
| 34. | Total capacity of conservator | Ltrs | 
 | |
| 35. | Total weight of Transformer | kg | 32500KG | |